SICK sensor faults: reading the LEDs and the type code before you replace the unit
GL10G IME inductive proximity sensor light curtain M4000 Standard microScan3 MLG-2 light grid photoelectric sensor PNP NPN safety laser scanner sensor troubleshooting SICK SICK sensors type code used industrial parts

SICK sensor faults: reading the LEDs and the type code before you replace the unit

11 November, 2026
SICK sensor faults: reading the LEDs

A line stops, the operator points at a sensor and says it is dead. On a SICK sensor you can usually settle that in ten seconds without a meter, because every one of them reports its state on the body. A single yellow LED on an inductive sensor means the output is switched. On the safety devices there is a 7-segment display or a screen carrying an actual fault, and that fault is the difference between a dirty lens and a unit that has to be replaced.

SICK sensor faults: reading the LEDs -  indicator

What the indicator is actually telling you

The colour conventions hold across the catalogue, which helps when you are in front of a family you have never configured.

Family Indicators Reading it
IME inductive One yellow LED Output state only. Lit means target detected. No LED with voltage present is a dead sensor or supply.
GL10G photoelectric Green, yellow Green is power, yellow is the received beam. Green alone with the reflector in place means the beam is not returning.
MLG-2 light grid Green, yellow Green is supply. Steady yellow means a beam is interrupted. Yellow flashing at 3 Hz is contamination or alignment mode: the signal is too weak.
M4000 sender Yellow, 7-segment Yellow is supply OK. A system error asks you to remove supply for three seconds before condemning the unit.
M4000 receiver Green, red, yellow, orange Green: beams clear, outputs on. Red: interrupted, outputs off. Flashing yellow: reset required. Orange: weak signal, clean or realign.
microScan3 Display, status LEDs The display names a fault type and a code. Heavy contamination of the optics cover is itself a fault and drops every safety output to OFF.

Two of those save an afternoon. Orange on an M4000 receiver and fast yellow flashing on an MLG-2 receiver are the optics complaining, not the electronics failing. Clean the lenses, check nothing has shifted the mounting, and most of those calls close without a part. Same for a contamination fault on a microScan3 Pro, where 100 per cent measured contamination switches the outputs off.

Read the type code before you order anything

An IME number is fully descriptive. Take IME12-04BPPZC0K: IME12 is the M12 thread, 04 is the 4 mm rated sensing distance, B is flush mounting (N where it is non-flush), P is a PNP output, and the second P is the output function, complementary, so this one gives a normally open and a normally closed signal from the same sensor on four wires. S in that position is a plain normally open, O is normally closed. C is the M12 male connector.

The last character catches people. K is a short body, S is standard length, and electrically they are the same sensor. A ...C0K is around 46 mm long with 29 mm of thread against roughly 65 mm and 48 mm for a ...C0S, so a short body dropped into a boss machined for a standard one has nothing left to lock a nut onto.

The same reading applies to the two M30 sensors on the shelf. IME30-20BPSZC0S is flush with 20 mm sensing, IME30-38NPSZC0S is non-flush with 38 mm. That distinction is not a preference: fit a non-flush sensor into a flush pocket and the surrounding metal sits inside its field, so it switches on its own mounting.

The number on the box is not always the number on the sensor. Our GL10G-P4252 is a set: the box number covers a retro-reflective sensor, a BEF-G10DC01 bracket and a P250 reflector, and the sensor inside is labelled GL10G-P4251. That is correct, not a mis-pick.

SICK sensor faults: reading the LEDs hands on

The substitutions that get a machine into trouble

Light grids and laser scanners look interchangeable in a photograph. They are not. The MLG-2 is an automation light grid and SICK states plainly that it is not a safety component under the Machinery Directive, so it must not protect people or guard access to a hazardous area. The S10B-9011DA from the S100 series is a measuring scanner for building automation, not a safety laser scanner. Both are good at detecting objects, and neither belongs where an M4000 or a microScan3 was, whatever the mounting holes say.

The second trap is buying half a system. M40E is a receiver. Its partner sender is M40S-034000AR0, a separate article number, and the pair has to agree: the 034000 in M40E-034000RT0 means three beams at 400 mm separation, so a four-beam receiver will never work against a three-beam sender. An MLG-2 is likewise ordered as a matched sender and receiver set.

Then there is the replacement that arrives working and still refuses to run. A fresh M4000 Standard comes with external device monitoring activated and the restart interlock set to internal. If your machine does contactor monitoring in a safety relay and expects the sensor to have no interlock of its own, the new unit sits in lock-out until it is configured to match the old one. On a microScan3 that is solved for you: the configuration memory lives in the system plug, so leave the plug and cabling on the machine, fit the new scanner to it, and it reads the configuration back on power-up.

Quick answers

My inductive sensor has no LED at all. Is it dead?

Not necessarily. The yellow LED on an IME shows output state, so an unlit sensor with no target in front of it is behaving normally. Present a steel target closer than the rated distance and watch again. If there is still nothing, measure the supply at the connector, because 10 to 30 V DC at the sensor is the one thing the LED cannot report.

Why does my new PNP sensor read nothing on the input card?

A PNP sensor sources the positive to the load and needs a sinking input, an NPN sensor does the opposite, and that letter sits in the middle of the type code. The output function matters just as much: an S normally open and an O normally closed give inverted logic in the same housing. Our guide to Siemens S7 CPU LED faults covers the controller end.

The light grid flashes yellow and the machine runs. Should I replace it?

No. Fast yellow flashing on the receiver means the received signal is weak but still sufficient. Clean both optical faces, confirm nothing has moved the brackets, and look for a new heat source or a bright lamp in line with the beams. Replacing the unit while the cause is still there buys a repeat call.

Can I put a 4 mm sensor where a 20 mm one was?

Only if you can move it closer. Rated sensing distance is measured against mild steel, and stainless, aluminium and brass all reduce it by a published factor, aluminium to roughly half. A shorter range sensor at the original gap gives you a machine that works in the morning and fails when the cabinet warms up.

Is surplus stock acceptable for safety devices?

Treat provenance as part of the specification. Match the full type code and the SICK article number, and have the installation validated before the guard goes back into service. Our used industrial parts buying guide covers what to ask for.

SICK sensor diagnostic

A diagnostic order that works

  1. Read the indicators before touching anything, and write down the colours and whether they are steady or flashing.
  2. Measure the supply at the sensor connector, not at the terminal rail.
  3. Present a target by hand and watch the output LED change state. That separates a sensor fault from an alignment or mechanical fault.
  4. On optical devices, clean both faces and check alignment before anything else.
  5. On a safety device, note the 7-segment code or the display fault and look it up in the operating instructions for that exact variant.
  6. Photograph the label and the configuration of the old unit before removing it.
  7. Quote the full type code, including the final letter, plus the SICK article number, and have any protective device validated after installation.

Got a type code and a line waiting? Send us the full code from the label and we will tell you what is on the shelf. Browse safety relays and contactors for the evaluation side, modules and cards for the input end, or contact us directly. Our SICK sensor stock is new or new surplus, ships from EU stock, and carries a 30-day functional warranty. Orders placed before 14:00 CET on a business day are dispatched the same day.

Related reading on Samonde

Sensors are the cheapest thing in the cabinet and the most frequently blamed. The LED on the body has usually already named the problem, and the type code says what to put in the van. SICK publishes a datasheet and operating instructions for every article number, so the last word on any variant is one search away. Read the body, then the label, then order.

Master